Steam generators

Type: three-pass smoke coil, horizontal execution, forced circulation

Capacity: 200 kg/h - 3,000 kg/h - 155 Kw - 2,250 Kw

Design Pressure: 1 bar - 11.76 bar

Temperature: 20 C° - 190.7 C°

Standard equipment:

  • Burner power cut-off thermostat
  • Water/steam side block pressure switch
  • Steam/fumes side block thermostat
  • INAIL approved safety valve
  • Water side block level switch
  • Water-steam inlet heat exchanger
 

Technical Specifications

 
 
IV200IV400IV650IV800IV1000IV2000IV3000
DimensionsWidth (mm)1050125013501350150017002000
Length (mm)1650195020002500250032504600
Height (mm)1050120013001300140017001800
Weight (Kg)600100013001500230035004800
Water inlet1" - DN 251" - DN 251" - DN 251" - DN 251" - DN 252" - DN 502" - DN 50
Steam outlet1 1/2" - DN 40
1 1/2" - DN 40
1 1/2" - DN 40
1 1/2" - DN 40
1 1/2" - DN 40
3" - DN 803" - DN 80
Condensate drain1/2" - DN 151/2" - DN 151/2" - DN 151/2" - DN 151/2" - DN 152" - DN 502" - DN 50
Fume outletϕ 180 ϕ 200ϕ 200ϕ 200ϕ 200ϕ 300ϕ 300
Steam production200 KG/H400 KG/H650 KG/H800 KG/H1000 KG/H2000 KG/H3000 KG/H
Capacity Kcal132.000 Kcal265.000 Kcal425.000 Kcal525.000 Kcal630.000 Kcal1.290.000 Kcal1.935.000 Kcal
Capacity kW154 Kw308 Kw494 Kw610 Kw732 Kw1.500 Kw2.249 Kw
Operating pressure1 - 11.76 bar1 - 11.76 bar1 - 11.76 bar1 - 11.76 bar1 - 11.76 bar1 - 11.76 bar1 - 11.76 bar
Steam temperature120.4 - 190.7 °C120.4 - 190.7 °C120.4 - 190.7 °C120.4 - 190.7 °C120.4 - 190.7 °C120.4 - 190.7 °C120.4 - 190.7 °C
Safety valve1" -1 1/2"
DN 25 - 40
1" -1 1/2"
DN 25 - 40
1" -1 1/2"
DN 25 - 40
1" -1 1/2"
DN 25 - 40
1" -1 1/2"
DN 25 - 40
1 1/4" - 2"
DN 32 - 50
1 1/4" - 2"
DN 32 - 50
PumpsN. 1N. 1N. 1N. 1N. 1N. 2N. 2
Voltage1 PH 230V / 3 PH 380V1 PH 230V / 3 PH 380V3 PH 380V3 PH 380V3 PH 380V3 PH 380V3 PH 380V
Power consumption1.3 Kw1.5 Kw1.7 Kw2.7 Kw3.5 Kw5 Kw5 Kw
Connection2P +T / 3P+N+T 16A2P +T / 3P+N+T 16A3P+N+T 16A3P+N+T 16A3P+N+T 16A3P+N+T 32A3P+N+T 32A
 

Optional accessories

As burner suppliers, we rely on leading companies such as Riello Spa and Baldur Spa or follow specific indications provided by our customers.
Our steam generators can be equipped with two-stage, three-stage, and modulating burners.
Modulation allows the generator's power to vary from 10% to 100%. With this system, the boiler will produce the exact amount of steam without waste, reducing consumption.

This is a water-fume heat exchanger that allows for efficiency increases of up to 5%.
Installation and configuration are carried out according to the customer's needs.

The electrical panels are equipped with PLC and 4.0 Ready interface.
This ensures an internet connection via cable or full 4G field for data exchange, monitoring, assistance, and remote diagnosis.
Interconnectivity allows the working pressure to vary from 1 to 12 bar anywhere and at any time.

This kit is available for generators with a production capacity of up to 1500 Kg/h for a full exoneration from a licensed operator.
The components of this kit are: a second steam block pressure switch with heat flow interruption; a second steam block thermostat with heat flow interruption, a feed water conductivity monitoring device, and a flame control device.

EXONERATION FROM
LICENSED OPERATOR

All our steam generators are equipped with safety accessories that allow for an exoneration from a licensed operator for 72 hours. Additionally, for models up to 1500 Kg/h steam,

they can be equipped with devices provided for by the reference regulations (DM. 07 August 2020) that allow for total exemption from a licensed operator.


MODULATION FROM 10% TO 100%

Modulating burners with an electronic cam allow for a modulation of the working range from 10% to 100%. This enables the boiler to produce the required steam without waste

, significantly reducing annual costs and consumption by up to 15%.


TECHNOLOGY AND INTERCONNECTION

Our generators and containerized plants are equipped with PLC and touch panel. This allows for an internet connection to exchange data, monitor, and ensure continuous

remote assistance and diagnosis. Furthermore, from the panel, it is possible to vary the working pressure (from 1 bar to 12 bar) at any time, even remotely.


Do you want a complete,
easy and quick to install plant?
Choose the container thermal room!

Contact us

If you have any questions, inquiries, or would like to learn more about our products, please feel free to contact us.

Just fill in the form. Our team will be ready to assist you and provide all the answers you need.

    I accept the processing of my data for the purpose of receiving promotional communications and offers relevant to my interests, also by e-mail

    Pursuant to GDPR 2016/679, I confirm that I have read, understood and consented to the privacy policy